gst conventional Accessories
DC-M9413 Series Wall Mount Sounder Strobe Installation Sheet (UL)
Description
The DC-M9413 Series Wall Mount Sounder Strobe is a fire alarm
notification appliance that is designed for mounting on indoor walls.
See Table 1 for a list of model numbers.
Table 1: Models
Description | Model number |
Sounder-strobe,15 to 110 multi-cd, white | DC-M9413W |
Sounder-strobe,15 to 110 multi-cd, ,red | DC-M9413R |
There are field-configurable options for selecting dB output, sounder
signal, and strobe signal output.
The strobe includes a field-configurable switch for selecting the desired
candela output. The candela output setting is locked in place and
remains visible after final installation.
This strobe features an enhanced synchronization circuit to comply
with the latest requirements of UL 1971 Signaling Devices for the
Hearing Impaired.
Synchronized operation requires that you connect the DC-M9413
Series Wall Mount Sounder Strobe to a NAC output set for Synch
Mode, or to a separate DC-M9410 Signal Synchronization Module.
Specifications
Operating Voltage | 24 VDC or 24 VFWR nominal |
Operating sounder strobe current |
See Table 5 |
Sound level output | See Table 2 |
Audible directional characteristics |
See Table 3 and Table 4 |
Light output | Selectable at 15, 30, 75, and 110 cd |
Synchronization | Meets UL 1971 requirements. Maximum allowed resistance between any two devices is 20 Ω. Refer to specifications for the synchronization control module, this strobe, and the control panel to determine allowed wire resistance. |
Strobe signal rate | 1 flash per second (fps) |
Wire size | 12 to 18 AWG (0.75 to 2.50 mm²) |
Compatible electrical boxes |
Single-gang box, 2-1/2 in. (64 mm) deep |
Operating environment Temperature Relative humidity |
32 to 120°F (0 to 49°C) 0 to 93% noncondensing |