Fire Alarm Control Panel

  • 2 Zone Hochiki FACP

2 Zone Hochiki FACP

Code: HCV-2 , HCV-4 , HCV-8
Manufacturers: Hochiki
Origin: UK
Download Catalogue: HCV-2, HCV-4, HCV-8 (112,19 KB)

DESCRIPTION

The HCV-2, HCV-4, HCV-8 series is available in a 2, 4, 8 Zone conventional panel design which is in accordance with BS EN54-2 and BS EN54-4 Detection and Fire Alarm Systems – Control and Indicating Equipment. The HCV series has an integrated Power Supply and Battery charging circuit. The control panel has “Voltage Free” Contacts for Fire and Local Fire which operate upon a fire condition. These are used for local control and signaling. In accordance with BS EN54-4. The HCV series are fully programmable using simple menu options. The Panel is a single board construction, which is installer friendly. Compatible with a wide range of detection devices. Remote control input terminals for Silence Alarm, Sound Alarm, Trouble and Reset..

STANDARD FEATURES

• Fully compliant with & tested to BS EN54-2 and BS EN54-4

• 2-wire repeaters and ancillary boards

• Fully programmable using simple menu options

• Simple, single board construction

• Installer friendly

• Compatible with wide range of detection devices

• Two monitored sounder outputs

• 3 Amp power supply

• Auxiliary power output

• Adjustable sounder delay time

• Sounder configuration options

• Zonal sounder delay detectors only

• Zonal sounder delay call points only

• Coincidence input selection

• I.S.Barrier selection by zone

• Short circuit fire by zone

• Non latching zones

• Silent zones

• Zone input delay

• General panel configuration SPECIFICATIONS

• Supply Voltage 230VAC (+10%/-15%)

• Power Supply DC Rating 24V 3 Amps

• Mains Supply Fuse 1.6 Amp 250V

• Dimensions 385mm(W) x 310mm(H) x 92mm(D)

• Weight 11.5 lbs.

• Color Red

• Material 1.2mm mild steel

• Max. Battery Size 7Ah 12V (2 per panel)

• Fault Contact Rating 30VDC 1 Amp

• Local Fire Contact Rating 30VDC 1 Amp

• Fire Contact Rating 30VDC 1 Amp

• Sounder Output Rating 0.5A per output (max 1.6A over all outputs)

• Detection Zone Current 1.6mA

• Detection Zone 6K8 5% end of line resistor

• Sounder Output 10K 5% end of line resistor

• Cable Capacity 2.5 mm per terminal

• Operating Temperature -5°C to + 50°C

• Operating Humidity 95% (non condensing)