To purchase

HCMC: +84-28-38 620 246
Email: sales@nhatnam.com.vn
No TT8, Tam Dao, Ward 15, District 10, Ho Chi Minh city

HA NOI: (84-24) 36.415.733
Email: chinhanh@nhatnam.com.vn
No B02, Nguyen Huu Tho, Hoang Mai district, Ha Noi

GST-Conventional-Detector

  • DC-M9103 Conventional Rate of Rise and Fixed Temperature Heat Detector (UL)

DC-M9103 Conventional Rate of Rise and Fixed Temperature Heat Detector (UL)

Code: DC-M9103
Manufacturers: GST
Origin: China

Features

 Reed switch testing.

 Output terminal for remote indicator available.

 Rate of rise and fixed temperature, and fixed temperature programmable.

 Complying with UL 521.

Description

DC-M9103 Conventional Rate of Rise and Fixed Temperature Heat Detector is a new generation product of GST. With built-in microprocessor, it works stably by being fixed with highly reliable fire judging program. On detecting a fire signal, it can change its own current to transmit the signal to fire alarm control panel (FACP) or addressable zone monitor unit. The detector keeps illuminating fire LED until it is reset by power-down. Connection and Wiring The detector connects with UL-certified products such as modules and control panels

Specification

Operating
Voltage
24VDC(16VDC - 28VDC)
Standby Current ≤ 60μA
Alarm Current ≤ 55mA
Fire LED Red, periodically flash once in
polling when the status is set to
“ON”; don’t illuminate when the
status is set to “OFF”. Periodically
flash twice in fault; illuminate in
alarming
.
Sensitivity Action Temperature:135°F
(57.2°C)
Response rate of rise:15°F /min
(8.3°C /min)
Maximum spacing 50 ft. (15.2 m)
Remote
Indication Output
Polarity-sensitive output ,Directly
connecting with remote indicator
(built in 10k resistor in series,
maximum output current is
2.0mA);
The remote indicator does not
illuminate in normal and flashes in
alarm.
Class and Setup Rate of rise and fixed temperature
(default), and fixed temperature
programmable.
Maximum Ripple
Voltage
2V ( peak-to-peak)
Alarm Reset Instantaneous cut-out (10s Min,
1.0VDCMax.)
Power-up Time ≤ 10s
Wiring Polarized 2-core for loop.
Ingress
Protection Rating
IP2X
UL Temperature
Range
32°F (0°C) - 100°F (37.8°C)
0 - 95%, non-condensing
Operating
Temperature
14°F (-10°C) - 122°F (+50°C)
0 - 95%, non-condensing
Mounting Hole
Spacing
45mm - 75mm
Weight About 110g (with base)