gst conventional Accessories
DC-M9415 Series Wall Mount Strobe Installation Sheet (UL)
Description
The DC-M9415 Series Wall Mount Strobe is a visible fire alarm
notification appliance that is designed for mounting on indoor walls.
See Table 1 for a list of model numbers.
Table 1: Models | |
Description | Model number |
Strobe, white | DC-M9415W |
Strobe, red | DC-M9415R |
The strobe includes a field-configurable switch for selecting the desired
candela output and a field-configurable jumper for the strobe signal
output. The candela output setting is locked in place and remains
visible after final installation.
This strobe features an enhanced synchronization circuit to comply
with the latest requirements of UL 1971 Signaling Devices for the
Hearing Impaired.
Synchronized operation requires that you connect the DC-M9415
Series Wall Mount Strobe to a NAC output set for Synch Mode, or to a
separate DC-M9410 Signal Synchronization Module.
Specifications
Operating voltage | 24 VDC or 24 VFWR nominal |
Strobe operating current | See Table 2 |
Light output | Selectable at 15, 30, 75, and 110 cd |
Synchronization | Meets UL 1971 requirements. Maximum allowed resistance between any two devices is 20 Ω. Refer to specifications for the synchronization control module, this strobe, and the control panel to determine allowed wire resistance. |
Strobe signal rate | 1 flash per second (fps) |
Wire size | 12 to 18 AWG (0.75 to 2.50 mm²) |
Compatible electrical boxes |
Single-gang box, 2-1/2 in. (64 mm) deep |
Operating environment Temperature Relative humidity |
32 to 120°F (0 to 49°C) 0 to 93% noncondensing |