GST Fire Alarm control panel

  • GST200-2/1 Intelligent Fire Alarm Control Panel

GST200-2/1 Intelligent Fire Alarm Control Panel

Code: GST200-2/1
Manufacturers: GST
Origin: China

GST200-2 Intelligent Fire Alarm Control Panel (FACP) is designed to comply with EN 54-2 standard with qualities of simple installation, operation, and easy maintenance. It is used in fire alarm system with the following features:  It controls at most 30 zones. Each zone has its own alarm and fault/disable LEDs and a label.  Maximum two Class A loops. The first loop can have up to 235 addressable devices, and the second up to 242 devices. It is compatible with a series of addressable GST products, which are intelligent sounder strobe (I-9403) complying with EN 54-3, rate of rise and fixed temperature heat detector (I-9103) complying with EN 54-5, photoelectric smoke detector (I-9102) complying with EN 54-7, intelligent manual call point (I-9202) complying with EN 54-11, intelligent reflective beam detector (I-9105R) complying with EN 54-12, input and output module (I-9300, I-9301) complying with EN 54-18, and loop isolator (C-9503) complying with EN 54-17.  The LCD can display 8 lines in total and 18 characters each line, assisting the 15 LEDs in displaying important information.  The memory does not lose data even if power supply is accidentally removed.  It has manual keys for each zone, which can activate/silence the sounder strobes separately.  Automatically prompting operation steps for every alarm device and for smoke exhaust and fire extinguishing equipment by field programming.  Sounder strobe interface provides 0.5A/24V output, compatible with GST conventional sounder strobe (C-9403) designed according to EN 54-3.  RS232 interface enables communication with PC.  RS485 interface enables networking.

2.1 Operating Voltage  Input Voltage: 220V/230VAC+10% -15%  Frequency: 50Hz/60Hz  Input Current: 0.5A  Fuse: 2A delay  Recommended Wiring: 1.5mm2 or above screened cable, complying with local installation code. 2.2 Standby Batteries  Maximum Charge Current: 1.2A  Maximum Charge Voltage: 27.6V  Type: Sealed lead acid batteries  Maximum Charge Capacity: Two 12V/21Ah batteries  Recommended manufacturer and model of battery: Power-Sonic PG12V21  Maximum Internal Resistance: 1Ω  Quiescent Current under Full-loaded Condition: 0.75A  Maximum Battery Operating Current: 2.82A  Recommended Wiring (subject to local installation codes):  GST fire cable  Vencroft Gold and Platignum  Nexans NX 200 and 200 Plus (LPCB tested)  Prysmian FP 200 and 200 Gold  Draka Firetuf and Firetuf Plus And all LPCB approved Fire cables 2.3 Communication Loop Parameters 2.3.1 RS485 Communication Loop  NETWORK (A, B): Communication cable for connecting with up to 32 network FACPs.  REPEATER (A, B): Communication cable for connecting with up to 10 repeater panels.  Recommended Wiring (subject to local installation codes):  GST fire cable  Vencroft Gold and Platignum

 Nexans NX 200 and 200 Plus (LPCB tested)  Prysmian FP 200 and 200 Gold  Draka Firetuf and Firetuf Plus And all LPCB approved Fire cables  Recommended Cable Length ≤1000m 2.3.2 RS232 Communication Loop RS232 communication loop is connected with a PC for running GstGMC2.0 Graphic Monitor Center (GMC) system PC through a DB9 port. Recommended Wiring: Standard RS-232 interface. The 2nd pin (for sending data), the 3 rd pin (for receiving data), and the 5th pin (ground) are connected with PC through three-core shield cable. Note: Wire length should be less than 15m; the screening layer and computer’s enclosure should be earthed. 2.4 Detection Loop Parameters  LOOP OUT (+, -): Polarized signal cable from the FACP connecting up to 235 addressable devices.  LOOP IN (+, -): Polarized signal cable returning to the FACP.  Output Voltage: 21V~27V pulse  Output Current: 0mA~300mA  Type of Loop: Class A loop  Recommended Wiring (subject to local installation codes):  GST fire cable  Vencroft Gold and Platignum  Nexans NX 200 and 200 Plus (LPCB tested)  Prysmian FP 200 and 200 Gold  Draka Firetuf and Firetuf Plus And all LPCB approved Fire cables.  Recommended Cable Length ≤1000m 2.5 Output Loop Parameters  Recommended Wiring (subject to local installation codes):  GST fire cable  Vencroft Gold and Platignum  Nexans NX 200 and 200 Plus (LPCB tested)  Prysmian FP 200 and 200 Gold  Draka Firetuf and Firetuf Plus And all LPCB approved Fire cables  Recommended cable length ≤1000m 2.5.1 FIRE ALARM OUTPUT (+, -)  Output Voltage: 21VDC ~27VDC  Output Current: 0mA~500mA

stallation and Operation Manual Page 6  End of Line Resistor: 4.7kΩ 2.5.2 F.P.E. OUTPUT (+, -)  Output Voltage: 21VDC ~27VDC  Output Current: 0mA~500mA  End of Line Resistor: 4.7kΩ 2.5.3 SOUNDER CIRCUIT OUTPUT (+, -)  Output Voltage: 21VDC ~27VDC  Output Current: 0mA~500mA  End of Line Resistor: 4.7kΩ 2.5.4 FAULT OUTPUT (NC, COM, NO)  Contact Capacity: 24VDC @1.0A  In fault state, NC and COM open, NO and COM close. 2.6 Dimensions 420mm×580mm×202mm