GST Fire Alarm control panel

  • 2/4 loop Fire Alarm Control Panel

2/4 loop Fire Alarm Control Panel

Code: GST5000W
Manufacturers: GST
Origin: China
Download Catalogue: Trung tâm GST5000W (265,05 KB)

Description:

The GST 5000 Two and Four loops addressable fire detection control panel is modular type Intelligent Fire Alarm Control Panel. The GST 5000 provides a high quality solution at Exceptional value. By utilizing advanced GST Protocol, the system is compatible with the complete range of GST intelligent detectors, Sounders, Call Points, Interfaces, including intrinsically safe and gaseous extinguishing control. GST 5000 is manufactured and certified to EN54 parts 2 and 4 and to BS5839 Par 4. The GST programming facilities enables advanced and complex cause and effects to be programmed with ease, including phased and cascade evacuation scenarios. The GST zonal indication and control facilities allow the operator to manually intervene, with evacuation and control of each zone including control of all plant equipment under an alarm condition. Addressable security control facilities and gas release control monitoring are built in as standard, making the system ideal for many applications such as Banks, Shops, Telecommunication Centers and GSM exchanges, industrial and commercial facilities. By utilizing the GST protocol the GST5000/2/4 can be networked with up to 32 panels, not only the GST200 single loop panel, but also with the GST200/2 twin Loop panel and the GST5000 modular 20 loop controller. Making this the perfect solution for large decentralized systems such as Shopping Centers Military campus industrial complexes, Holiday villages etc.


Features and Benefits

1. Graphical LCD Display.

2. 60 Zone indication including manual intervention and control panel.

3. 3 programmable alarm output

4. Networked with all GST Intelligent Fire panels

. 5. Programmable form PC or via on board keypad.

6. RS485 Bus Output ( Max. 64 Repeaters)

7. Built-in gas extinguishing control.

8. Integrated Security alarm facilities.

9. Advanced user-friendly programming software including ‘Fuzzy Logic’.

10. Optional Color Graphics.

11. Optional Fireman’s Control Panel.

12. Panel Printer included

13. Optional Color Graphics.

14. Optional Fireman’s Control Panel.

15. GST5000/2 Two loops can connect up to 480 Addresses 16. GST5000/4 Two loops can connect up to 960 addresses


Technical Specification

Standard EN54 Part 2/4 ; BS5839 Part 4 Loop Capacity GST5000/2:480 addresses GST5000/4:960 addresses

Loop Length 1.2Km using 1.5 mmsq.

Main Input Voltage 220 ± 10% VAC 50/60 Hz

Input Current Rating 1.5A

System Operating Voltage 24 VDC Nominal (17-29 VDC)

Standby Batteries 2 x 12AH, 24 hours

Sounder-Alarm Circuits (3) Settable dry contact or 24Vdc Output Output voltage 17 to 29 VDC Output current: 1.0A Maximum total load 1.5A AOL 10K resistor

Fuses Mains 1A (20mm A/S ceramic) Sounders (2): 1A (20mm A/S) Fire alarm Output 0.5A (20mm A/S) Battery: 2A (20mm A/S HRC ceramic)

(Fire alarm) Relay Output 0.5A at 24VDC

Common Fault Relay Output Volt-free changeover 1.0A at 24 VDC

24 VDC Fused Output Maximum load 500mA at 17-28VDC

Battery Charging Current Limit 600mA

Dimension 500mm x 700mm x 170 mm 