GST Addressable Module
DC-9503E Loop Isolator
Features
Isolation of short circuit, automatic restore when short circuit is cleared.
Maximum output current is 1A.
DIN-Rail mounted or Wall mounted.
Standard: EN 54-17:2005
Description
In fire alarm system, such condition often occurs that partial short circuit of loop affects the whole system. DC-9503E Loop Isolator(hereinafter referred to as the isolator)can isolate the shorted circuit from the whole system to ensure normal operation of other devices and help locate the devices in fault. After the short circuit fault is cleared, those devices will be re-introduced into the system. The isolator is suitable for use in the loop of addressable fire alarm system.
Connection & Cabling
(I+, I-) IN & OUT: input signal loop, I+ is positive and I - is negative.
O+, O-: output signal loop, O+ is positive and O- is negative.
Recommended Wiring: 1.0mm2 or above twisted pair. Wires should not be laid out in the same conduit or raceway with Class 1 wires such as power cables, high and low voltage distribution cables and so on.